Hollow fiber ultrafiltration membranes provide sterilized water where bacteria, parasites and viruses are safely removed — even with fluctuating water quality, as can occur aſter heavy rainfall. The quality of the filtrate remains consistently good! In potable water treatment, the filtration process is ideally used before final disinfection.
In regular cycles, back washes are performed to prevent blockages in the modules. Cleaning is supported by the addition of chemicals, where necessary, and adapted to the raw water quality present.
AP-UF suits for
Extra benefits
More reasons why this high technology solution gets along with your requirements
Technical specification of AP-UF 20000
MODEL | AP-UF 5000 | AP-UF 20000 |
---|---|---|
Filtration capacity*, L/hour | 2000 to 6000 | 12 000 to 25 000 |
Membrane Quantity | 1 | 4 |
Membrane surface, m2 | 60 | 4 × 60 |
Membrane material | Modified PES | Modified PES |
Nominal pore size, µm | 0.02 | 0.02 |
*Filter performance depends on the water quality
Suitable for the following feed water parameters:
Parameter | Value |
---|---|
pH range | 3.0 – 12.0 |
Free chlorine | < 1.2 mg/l |
Turbidity | < 30 NTU |
Dissolved Organic Carbon (DOC) | 0.5 - 12 mg/l |
Suspended solids | < 50 mg/l |